Cable Size Selection for Motors & Industrial Loads: kW to Current, Derating and Voltage Drop
A step-by-step method to size LT cables for motors and industrial loads — full-load current, derating, voltage drop and starting current — with a quick kW-to-amps table and a worked example.
Source: Standard electrical engineering practice; manufacturer cable catalogues; typical project specifications, as of November 2026. Always follow the project’s design basis.
WHAT THIS GUIDE COVERS
- Why Cable Sizing Goes Wrong in Industrial Projects
- Step 1: Calculate Full-Load Current
- Step 2: Apply Design Margin and Derating
- Step 3: Check Voltage Drop
- Step 4: Check Starting Current and Short Circuit
- Quick Reference: Motor kW to Current
- Copper vs Aluminium and Armoured vs Unarmoured
- Worked Example: 37 kW Pump Motor
An undersized cable does not fail on day one. It runs hot, drops voltage, makes motors struggle to start, and slowly ages its own insulation. An oversized cable wastes money on every metre. In industrial projects with long runs, getting the size right is worth lakhs.
This guide walks through the method electrical designers use to size LT cables (up to 1.1 kV) for motors and industrial loads — in plain steps, with a worked example.
1. Why Cable Sizing Goes Wrong in Industrial Projects
- Using the catalogue rating without derating — ratings assume standard conditions that rarely match site reality.
- Ignoring route length — a cable that is fine at 20 m can fail the voltage-drop check at 200 m.
- Forgetting motor starting current — direct-on-line starts pull several times full-load current.
- Copying sizes from a previous project with different loads, ambient temperature or laying method.
2. Step 1: Calculate Full-Load Current
For a three-phase motor, full-load current (FLC) is:
Where P is the motor’s rated output, V is the line voltage (415 V in most Indian plants), and power factor and efficiency come from the motor nameplate. Always use nameplate values when available — the example values in this guide are assumptions.
3. Step 2: Apply Design Margin and Derating
Two adjustments turn FLC into the current the cable must actually carry.
Design margin
Many designers size motor feeders at about 125% of full-load current to allow for continuous duty and minor overloads. Follow your project’s design basis.
Derating factors
| FACTOR | WHY IT MATTERS | WHERE TO FIND IT |
|---|---|---|
| Ambient / ground temperature | Hotter surroundings reduce how much current a cable can safely carry | Manufacturer derating tables |
| Grouping | Cables laid together heat each other | Manufacturer grouping factors |
| Laying method | In air, on trays, in ducts or buried — each rates differently | Manufacturer rating tables by installation type |
| Depth of laying | Deeper buried cables dissipate heat differently | Manufacturer tables for buried cables |
| Soil thermal resistivity | Dry or rocky soil holds heat | Manufacturer correction factors |
Source: Manufacturer cable catalogues and standard design practice, as of November 2026.
Multiply the individual factors together. The required catalogue rating is the design current divided by the combined derating factor.
4. Step 3: Check Voltage Drop
Long cable runs lose voltage. Too much drop means motors draw more current, run hotter and may fail to start. A quick check uses the catalogue’s millivolt-per-amp-per-metre (mV/A/m) value:
Compare the result with the limit in your specification — power circuits are commonly limited to about 3–5% of supply voltage. If the drop is too high, step up one cable size and recheck.
5. Step 4: Check Starting Current and Short Circuit
- Starting current: DOL-started motors typically draw about 6–8 times FLC for a few seconds. Check the voltage dip at the motor during starting, especially on long runs. Star-delta or soft starters reduce this.
- Short-circuit withstand: the cable must survive the prospective fault current until the protective device clears it. Check against the breaker’s clearing time and the cable’s short-circuit rating.
- Protection coordination: the breaker or MCCB rating must protect the cable, not just the motor. See how to choose MCBs for basic coordination.
6. Quick Reference: Motor kW to Current
| MOTOR RATING | FULL-LOAD CURRENT (CALCULATED) | WITH 125% DESIGN MARGIN |
|---|---|---|
| 5.5 kW (~7 HP) | 10.0 A | 12.5 A |
| 7.5 kW (~10 HP) | 13.6 A | 17.0 A |
| 11 kW (~15 HP) | 20.0 A | 25.0 A |
| 15 kW (~20 HP) | 27.3 A | 34.1 A |
| 22 kW (~29 HP) | 40.0 A | 50.0 A |
| 37 kW (~50 HP) | 67.3 A | 84.1 A |
| 55 kW (~74 HP) | 100.0 A | 125.0 A |
| 75 kW (~101 HP) | 136.4 A | 170.5 A |
Source: Headsup B2B calculation at 415 V, 3-phase, assuming power factor 0.85 and efficiency 90%. Illustrative only — use motor nameplate values for actual design.
Use this table to estimate current — then select the cable from your chosen manufacturer’s derated rating table, not from a generic chart.
7. Copper vs Aluminium and Armoured vs Unarmoured
| CHOICE | WHEN IT FITS | TRADE-OFF |
|---|---|---|
| Copper conductor | Short to medium runs, space-constrained trays, motor terminations | Higher material cost, smaller size for same current |
| Aluminium conductor | Long feeders and large sizes where cost matters | Larger size for the same current; needs proper lugs and jointing |
| Armoured cable | Buried, outdoor or mechanically exposed routes | Heavier and costlier, but protected |
| Unarmoured cable | Indoor trays, conduits and protected routes | Lighter, cheaper, less mechanical protection |
Source: Standard industry practice, as of November 2026.
More detail: armoured vs non-armoured cable and HT vs LT cables.
8. Worked Example: 37 kW Pump Motor
ILLUSTRATIVE MODEL (HYPOTHETICAL) — 37 KW MOTOR, 150 M CABLE RUN
Hypothetical example with assumed values, for illustration only. Actual sizing must use motor nameplate data, the selected manufacturer’s rating and mV/A/m tables, and the project’s design basis — verified by a qualified electrical engineer.
⚠ COMMON MISTAKES
- Picking a size from the catalogue without applying derating factors.
- Skipping the voltage-drop check on long runs.
- Sizing for running current but ignoring DOL starting current.
- Using generic charts instead of the selected manufacturer’s tables.
- Protecting the motor but not the cable with the breaker rating.
KEY TAKEAWAYS
- Start with full-load current from the motor nameplate.
- Apply a design margin and every relevant derating factor.
- Choose from the selected manufacturer’s derated rating table.
- Check voltage drop on every long run.
- Account for starting current and short-circuit withstand.
- Get final sizes verified by a qualified electrical engineer.
Choosing a cable brand? See top cable companies in India.
Need LT Power Cables for Your Project?
✓ Copper & aluminium, armoured & unarmoured ✓ Verified suppliers across top brands ✓ Pan-India delivery
Disclaimer: This guide explains general cable-sizing methodology for information only. Values in examples are assumptions. Cable sizing for any installation must be carried out by a qualified electrical engineer using motor nameplate data, manufacturer rating tables and applicable standards and codes.